Home/Tools/Wire Size Calculator

Wire Size Calculator — NEC Ampacity

Minimum conductor size for any amp load based on NEC Table 310.16. Picks copper or aluminum and handles 60°C, 75°C, and 90°C terminations.

Minimum conductor
— A rated
Required ampacity
A
Termination ampacity
A
After derating
A
// Ad slot — fills after AdSense approval

How NEC wire sizing actually works

Picking a conductor is a two-rule check. The conductor has to (1) carry the load without overheating, and (2) be no smaller than the lowest-rated termination on the circuit. Get both right and you've satisfied NEC 110.14(C) and NEC 310.15.

Step 1 — Required ampacity

For continuous loads (anything drawing current for 3 hours or more), the conductor and overcurrent device must be sized at 125% of the load per NEC 210.19(A) and 215.2(A). Non-continuous loads use the load value directly.

Required ampacity = Load × 1.25 (continuous) Required ampacity = Load × 1.00 (non-continuous)

Step 2 — Termination column

Look up the conductor in NEC Table 310.16 using the column matching the lowest termination rating in the circuit. For most equipment up to 100 A, that's the 60°C column. For commercial equipment marked "75°C only" or "60/75°C," use 75°C. The 90°C column exists only as a starting ampacity for derating — you can never terminate to it.

Step 3 — Ambient and conduit derating

When the ambient or the conduit fill is harsher than the 30°C baseline / 1–3 conductors baseline, apply correction factors to the 90°C ampacity, then make sure that derated value still meets the load.

Derated ampacity = 90°C ampacity × Ambient factor × CCCs factor

Your final conductor pick is the smaller of: (a) the size whose 60/75°C ampacity meets the required ampacity, and (b) the size whose derated 90°C ampacity meets the required ampacity. The bigger of those two minimums is what you install.

Step 4 — Voltage drop (separate check)

NEC 210.19 informational note recommends total branch + feeder voltage drop ≤ 5%. Long runs may need to upsize beyond what ampacity alone requires. Use the Voltage Drop Calculator to verify.

NEC Table 310.16 — common ampacities

Insulated conductors rated up to 2000 V, not more than three current-carrying in a raceway, ambient 30°C (86°F).

SizeCu 60°CCu 75°CCu 90°CAl 60°CAl 75°CAl 90°C
14 AWG152025
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115657585
2 AWG951151307590100
1 AWG11013014585100115
1/0125150170100120135
2/0145175195115135150
3/0165200225130155175
4/0195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350

Per NEC 2023 Table 310.16. Verify against the NEC edition adopted in your jurisdiction. This page is a decision aid — confirm with the AHJ before energizing.

Frequently asked questions

What wire size for 50 amps?
6 AWG copper or 4 AWG aluminum at 75°C terminations. 8 AWG copper hits 50 A only at 75°C — check what your breaker is rated for.
60°C vs 75°C vs 90°C?
Insulation temperature ratings. Use the lowest-rated termination per NEC 110.14(C). The 90°C column is just a starting point for derating.
How does conduit fill change wire size?
Above 3 current-carrying conductors in a raceway, ampacity gets reduced — 80% for 4–6, 70% for 7–9, 50% for 10–20, and so on per NEC 310.15(C)(1).
Copper or aluminum for service?
Aluminum is cheaper and standard for 200 A residential. Use AL9CU lugs and antioxidant compound. Otherwise stick with copper.
Why is my breaker bigger than my load?
Continuous loads are sized at 125% per NEC 210.19. A 32 A continuous load takes a 40 A breaker and 40 A-rated wire.
Does this include voltage drop?
No — ampacity only. Long runs need a separate voltage drop check, especially on 120 V circuits over ~60 ft.

Related tools