Home/Tools/Transformer kVA Calculator

Transformer kVA Calculator

Calculate required kVA from load amps and voltage, or find secondary amps from a known kVA rating. Single-phase and three-phase. Primary OCPD sizing per NEC 450.3.

Required kVA
kVA
Next std size
kVA
Primary FLA
Max primary OCPD
NEC 450.3
// Ad slot — fills after AdSense approval

Standard dry-type transformer sizes

kVA rating3Ø 480V sec. FLA3Ø 208V sec. FLA1Ø 240V sec. FLA
33.68.312.5
56.013.920.8
7.59.020.831.3
1012.027.841.7
1518.041.662.5
2530.169.4104.2
37.545.1104.0156.3
5060.2138.9208.3
7590.2208.2312.5
100120.3277.6416.7
150180.4416.4625.0
225270.6624.6937.5
300360.8832.81250.0
500601.41387.92083.3
750902.12082.03125.0
10001202.82775.94166.7

Transformer sizing explained

Transformers are sized in kilovolt-amperes (kVA), not kilowatts (kW). kVA is the apparent power — it's what the transformer actually has to handle regardless of power factor. The formulas:

Single-phase: kVA = (V × I) / 1000 Three-phase: kVA = (V × I × 1.732) / 1000 Primary FLA = kVA × 1000 / (V_primary × 1.732) [3-phase] Secondary FLA = kVA × 1000 / (V_secondary × 1.732) [3-phase]

Sizing rules of thumb

NEC 450.3 — Overcurrent protection

Transformers 1000V and below (the common dry-type distribution transformer):

Frequently asked questions

kVA vs kW — what's the difference?
kW is real power (what does actual work). kVA is apparent power (what the wiring and transformer have to handle). kW = kVA × power factor. A 100 kVA transformer at 0.8 PF delivers 80 kW of real power. Transformers are rated in kVA because they handle current regardless of power factor.
Can I parallel two transformers?
Yes, but they must have the same kVA rating, same impedance (within 10%), same voltage ratio, and same phase relationship (same winding configuration — delta-wye must match delta-wye). Mismatched impedances cause one transformer to take more than its share of load.
How do I calculate transformer inrush?
Transformer inrush (magnetizing inrush) occurs at energization and can reach 8–12× the transformer's full load current for several cycles. OCPD must be selected to ride through inrush — that's why NEC 450.3 allows 125–250% of FLA rather than the standard 100%.
What does transformer impedance affect?
Impedance (Z%) determines maximum available fault current at the secondary. Fault current ≈ FLA / (Z%/100). A 75 kVA, 480V, 3-phase transformer (90A FLA) at 5% impedance delivers: 90 / 0.05 = 1800A maximum fault current. This number affects downstream bus ratings and OCPD interrupt ratings.

Related tools