Home/Guides/NEC 310.16 Cheatsheet

NEC Table 310.16 Ampacity Cheatsheet

The conductor ampacity table every electrician references. Copper and aluminum at 60°C, 75°C, and 90°C — the full table, plus ambient temperature correction factors, conduit fill derating, and how to apply them correctly.

Table 310.16 — Copper conductors

Ampacity for not more than 3 current-carrying conductors in raceway, cable, or earth. Ambient temperature 30°C (86°F).

AWG / kcmil 60°C (140°F)
TW, UF
75°C (167°F)
THW, THWN, USE, RHW
90°C (194°F)
THHN, THWN-2, XHHW-2, USE-2
#14152025
#12202530
#10303540
#8405055
#6556575
#4708595
#385100110
#295115130
#1110130150
1/0125150170
2/0145175195
3/0165200225
4/0195230260
250 kcmil215255290
300 kcmil240285320
350 kcmil260310350
400 kcmil280335380
500 kcmil320380430
600 kcmil355420475
750 kcmil400475535
1000 kcmil455545615

Table 310.16 — Aluminum conductors

Same conditions as copper table above. Aluminum conductors are typically 2 sizes larger than copper for the same ampacity.

AWG / kcmil 60°C (140°F)
TW, UF
75°C (167°F)
THW, THWN, USE
90°C (194°F)
THHN, THWN-2, XHHW-2
#12152025
#10253035
#8304045
#6405060
#4556575
#3657585
#27590100
#185100115
1/0100120135
2/0115135150
3/0130155175
4/0150180205
250 kcmil170205230
300 kcmil190230255
350 kcmil210250280
400 kcmil225270305
500 kcmil260310350
600 kcmil285340385
750 kcmil320385435
1000 kcmil375445500

Ambient temperature correction factors

Table 310.16 is based on 30°C (86°F) ambient. In hotter environments — attics, outdoor conduit in Florida, industrial spaces near equipment — derate ampacity using these multipliers.

Ambient temp 60°C insulation 75°C insulation 90°C insulation
10°C or less (50°F)1.291.201.15
11–15°C (52–59°F)1.221.151.12
16–20°C (61–68°F)1.151.111.08
21–25°C (70–77°F)1.081.051.04
26–30°C (79–86°F)1.001.001.00
31–35°C (88–95°F)0.910.940.96
36–40°C (97–104°F)0.820.880.91
41–45°C (106–113°F)0.710.820.87
46–50°C (115–122°F)0.580.750.82
51–55°C (124–131°F)0.410.670.76
56–60°C (133–140°F)0.580.71
61–70°C (142–158°F)0.330.58
71–80°C (160–176°F)0.41
Corrected ampacity = Table ampacity × correction factor Example: #6 copper THWN (75A @ 90°C) in 45°C ambient Corrected: 75A × 0.87 = 65.3A

Conduit fill derating — more than 3 current-carrying conductors

Table 310.16 assumes 3 current-carrying conductors. Run more and you must derate — the conductors can't shed heat as easily when packed together.

Number of current-carrying conductors Ampacity multiplier
4–60.80 (80%)
7–90.70 (70%)
10–200.50 (50%)
21–300.45 (45%)
31–400.40 (40%)
41 and above0.35 (35%)

Note: Equipment grounding conductors do not count toward the fill derating. Neutral conductors count only if they carry unbalanced load (which is most of the time in mixed-load circuits).

Applying both factors at once

Final ampacity = Table ampacity × ambient factor × fill factor Example: 8 THWN-2 (#6 copper) conductors in EMT in a 40°C space Table ampacity at 90°C: 75A Ambient factor (40°C, 90°C insulation): 0.91 Fill factor (7–9 conductors): 0.70 Final: 75 × 0.91 × 0.70 = 47.8A

Apply both correction factors when both conditions are present. Always use the corrected ampacity to select conductor size — not the table value.

How to use the table — the right way

Step 1: Determine the termination temperature rating

Most equipment (panelboards, breakers, switches) is listed for 75°C terminations. Use the 75°C column to select your conductor, even if the wire insulation is THHN (rated 90°C). The 90°C column is only used for derating math (see below).

Step 2: Apply derating factors using the 90°C column

When derating for ambient temperature or conductor fill, start with the 90°C column (highest rated), apply the correction factors, and then verify that the final derated ampacity doesn't exceed the 60°C or 75°C column for your termination temperature.

Step 3: Apply continuous load rule

Loads that operate continuously for 3 hours or more require the conductor to be sized at 125% of load. A 60A continuous load requires a conductor rated for at least 75A. Size the conductor first, then verify it meets the 125% overcurrent rule for the OCPD (NEC 210.19, 215.3).

Continuous load: Conductor ampacity ≥ load × 1.25 Non-continuous: Conductor ampacity ≥ load × 1.00 Mixed: Conductor ampacity ≥ (continuous load × 1.25) + (non-continuous load)

Step 4: Select the OCPD

The OCPD (breaker or fuse) must not exceed the conductor ampacity — or if the conductor is derated below the standard breaker size, you use the conductor's derated ampacity to select the OCPD. Always use the lower of the conductor's allowable ampacity and the OCPD standard size that doesn't exceed it.

Common conductor sizing errors

The practical conductor sizing quick rule

Electricians carry these in their head for quick field estimates. They're not substitutes for the full calculation, but they'll get you in the right neighborhood fast:

Ampacity neededCopper (75°C) sizeAluminum (75°C) size
15A#14(not rated at 15A below #12)
20A#12#10
30A#10#8
40A#8#6
50–55A#6#4
70–85A#4#2
100A#1/0#2/0
125–130A#2/0#3/0
150A#3/0#4/0
175–200A#4/0250 kcmil
230A350 kcmil350 kcmil
310–320A500 kcmil600 kcmil

Related tools