Wire Size Calculator — NEC Ampacity
Minimum conductor size for any amp load based on NEC Table 310.16. Picks copper or aluminum and handles 60°C, 75°C, and 90°C terminations.
How NEC wire sizing actually works
Picking a conductor is a two-rule check. The conductor has to (1) carry the load without overheating, and (2) be no smaller than the lowest-rated termination on the circuit. Get both right and you've satisfied NEC 110.14(C) and NEC 310.15.
Step 1 — Required ampacity
For continuous loads (anything drawing current for 3 hours or more), the conductor and overcurrent device must be sized at 125% of the load per NEC 210.19(A) and 215.2(A). Non-continuous loads use the load value directly.
Step 2 — Termination column
Look up the conductor in NEC Table 310.16 using the column matching the lowest termination rating in the circuit. For most equipment up to 100 A, that's the 60°C column. For commercial equipment marked "75°C only" or "60/75°C," use 75°C. The 90°C column exists only as a starting ampacity for derating — you can never terminate to it.
Step 3 — Ambient and conduit derating
When the ambient or the conduit fill is harsher than the 30°C baseline / 1–3 conductors baseline, apply correction factors to the 90°C ampacity, then make sure that derated value still meets the load.
Your final conductor pick is the smaller of: (a) the size whose 60/75°C ampacity meets the required ampacity, and (b) the size whose derated 90°C ampacity meets the required ampacity. The bigger of those two minimums is what you install.
Step 4 — Voltage drop (separate check)
NEC 210.19 informational note recommends total branch + feeder voltage drop ≤ 5%. Long runs may need to upsize beyond what ampacity alone requires. Use the Voltage Drop Calculator to verify.
NEC Table 310.16 — common ampacities
Insulated conductors rated up to 2000 V, not more than three current-carrying in a raceway, ambient 30°C (86°F).
| Size | Cu 60°C | Cu 75°C | Cu 90°C | Al 60°C | Al 75°C | Al 90°C |
|---|---|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | — | — | — |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 |
| 1/0 | 125 | 150 | 170 | 100 | 120 | 135 |
| 2/0 | 145 | 175 | 195 | 115 | 135 | 150 |
| 3/0 | 165 | 200 | 225 | 130 | 155 | 175 |
| 4/0 | 195 | 230 | 260 | 150 | 180 | 205 |
| 250 kcmil | 215 | 255 | 290 | 170 | 205 | 230 |
| 300 kcmil | 240 | 285 | 320 | 195 | 230 | 260 |
| 350 kcmil | 260 | 310 | 350 | 210 | 250 | 280 |
| 400 kcmil | 280 | 335 | 380 | 225 | 270 | 305 |
| 500 kcmil | 320 | 380 | 430 | 260 | 310 | 350 |
Per NEC 2023 Table 310.16. Verify against the NEC edition adopted in your jurisdiction. This page is a decision aid — confirm with the AHJ before energizing.